WISE-4000 User Manual 138
Field Abbreviations Data type Property
Expansion bit
writing status
WEvt Number
The status for preview writing action.
*Event value 0x17: the writing process is not finish, user should poll the
status later.
Remarks:
Event
Value
(Bit: 6~0)
Description
0 (0x00) No error
1 (0x01) Illegal function
2 (0x02) Illegal data address
3 (0x03) Illegal data value
4 (0x04) Slave device failure
5 (0x05) Acknowledge
6 (0x06) Slave device busy
7 (0x07) Negative acknowledge
8(0x08) Memory parity error
9 (0x09) Reserved
10 (0x0A) Gateway path unavailable
11 (0x0B) Gateway target device failed to respond
12 ~15 Reserved
16 (0x10) Unavailable
17 (0x11) Slave response timeout
18 (0x12) Checksum error
19 (0x13) Reserved data error
20 (0x14) Send request fail
21 (0x15) Unprocessed
22 (0x16) Read only
23 (0x17) In processing