EasyManuals Logo
Home>Advantech>I/O Systems>WISE-4050/LAN

Advantech WISE-4050/LAN User Manual

Advantech WISE-4050/LAN
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
17 WISE-4000 User Manual
Chapter 2 Product Specifications
2.4 WISE-4060/LAN
2.4.1 I/O Specification
Digital Input
Channel: 4
Logic level
Dry Contact 0: Open
1: Close to DI COM
Wet Contact 0: 0~3 V
DC
or -3~0 V
DC
1: 10~30 V
DC
or -30~-10 V
DC
(3 mA min.)
Isolation: 3,000 V
rms
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
Keep/Discard Counter Value when Power-off
Supports Frequency Input Function (Maximum frequency 3 kHz)
Supports Inverted DI Status
Relay Output
Channels: 4 (Form A)
Contact Rating (Resistive Load)
–250 V
AC
@ 5 A
–30 V
DC
@ 3 A
Relay On Time: 10 ms
Relay Off Time: 5 ms
Insulation Resistance: 1 G min. @ 500 V
DC
Dielectric Strength
Between Contacts: 1000 V
AC
(1min)
Between Coil to Contact: 3000 V
AC
(1min)
Maximum Switching: 60 operations/minute
Supports Pulse Output
Supports High-to-Low and Low-to-High Delay Output

Table of Contents

Other manuals for Advantech WISE-4050/LAN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech WISE-4050/LAN and is the answer not in the manual?

Advantech WISE-4050/LAN Specifications

General IconGeneral
BrandAdvantech
ModelWISE-4050/LAN
CategoryI/O Systems
LanguageEnglish

Related product manuals