Table A-l. Error Messages (Cot-H)
ERROR
CODE
62*
63*
64*
65.
66*
67
I
68
70*
71
l
A message from the
1. Check cable connections between
controller to the
the programmer and controller and
programmer arrived
retry.
garbled.
2. Retry using another programmer.
To clear errors with an asterisk, press SHIFT/RESET; errors without an asterisk, press RESET.
(All errors can be cleared using the SHIFT/RESET sequence.)
1
L-
MEANING
An error is detected
in user logic during
the power up sequence.
REMEDY
1. Reattempt to start the con-
troller from the programmer
(SHIFT/RESET).
2. Reload the user logic from
the program pack.
3. Clear controller memory (SUPVI,
SUPVB, then SUPVP and reprogram
the controller.
A message from the
programmer to the
controller arrived
garbled.
A message sent by the
programmer has taken
too long to get to the
controller.
The transfer of user
logic between the
program pack and the
controller (or vice-
versa) was not
successful.
1. Check cable connections between
programmer and controller and
retry.
2. Retry using another programmer.
1. Check cable connections between
programmer and controller and
retry.
2. Retry using another programmer.
1. Check that program pack is inserted
correctly and retry.
2. When loading the controller,
this message indicates that con-
troller memory is bad.
3. When dumping to the program pack,
this message indicates that
program pack is faulty.
Insufficient power
(less than 100 (or
200) VAC).
If there is insufficient power, data
cannot be entered into the controller
(i.e., user logic cannot be altered).
The controller will continue to
function normally and the P370
Programmer will operate in the
Examine, Supervisory, and Error modes.
An attempt has been
made to disable a
coil (00Xx) and the
cursor is not
positioned on top
of a coil.
Move cursor to appropriate element and
retry. Coil contacts cannot be
individually disabled. They are all
disabled when the coil is disabled.
An attempt was made
to force a coil or
input contact that
was not previously
disabled.
Disable the element and retry.
A message sent by the
controller has taken
too long to get to the
programmer.
1. Check cable connections between the
programmer and controller and retry.
2. Retry using another programmer.
A-2