EasyManua.ls Logo

AEG Protect D Series - Page 12

AEG Protect D Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
WEIGHT AND DIMENSIONS
Protect D 6000
LCD
438x86.3x573
mm (
WxHxD)
14
kg
Protect D 10000
LCD
438x86.3x573
mm (WxHxD)
16
kg
Protect D 6000BP LCD
438x129x593
mm (WxHxD)
60
kg
Protect D 10000BP LCD
438x129x593
mm (WxHxD)
72
kg
ELECTRICAL INPUT
Selectable input Voltage range
208/220/230/240V
Voltage
at 100% Load
176~276Vac
Nominal frequency
50/60Hz auto
-
sensing
Frequency range
40 Hz
70 Hz,
for
≤60% rated load
45 Hz
55 Hz (50Hz system)
54 Hz – 66 Hz (60Hz system)
for >60% rated load
Bypass voltage range
176~264 Vac (default)
Noise
filtering
MOV for normal and common
mode noise
Input connection
Hardwired
Input cable
Not provided
ELECTRICAL INPUT CONNECTIONS
Protect D 6000
LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over
load)
230V / 32.3A
Up to 43A
Protect D 10000LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over load)
230V / 50.9A
Up to 70.1A

Table of Contents