84
Accuracy of control
Voltage ± 3%*
In the -15% to +10% range of the type voltage.
Current ±1.5%*
*always based on the end value
Limits
Voltage limit U
eff
Current limit I
eff
(for ...HRL1; ...HRLP1)
Power limit P (for ...HRLP1)
Peak current limit to Î=3xI
nom
at VAR mode
(for ...HRL1; ...HRLP1)
Relay outputs (only for ...H RL1 and ...H RLP1)
Changeover contact, contact material: AgSnO2 / Au plated
The relay can be used for low load circuits (> 5V 20mA), provided it
has not been preloaded with 230VAC.
Max. values: 250V, 6A, 180W, 1500VA
Insulation resistance 4kV / 8mm
Ambient temperature
35°C at ...F... (with forced cooling)
45°C with natural air cooling (without fan)
If the maximum ambient temperature is reduced, the maximum load
current can be increased up to 110% of the nominal current. The
following applies: 1% more current requires a temperature reduction
of 1°C.
The maximum ambient temperature can be increased up to a maxi-
mum of 55°C if the maximum load current is reduced. The following
applies: 1°C more ambient temperature requires a current reduction
of 2%. Use of the device in UL conditions up to a maximum ambient
temperature of 40°C.
Connection data, power connection
Grounding screw / nut for connecting the protective conductor to the
fixing adapter. Grounding also serves for EMC means (Y capacitor
4.7 nF).