06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 109 of 112
Modulex E8 Controller and BCM
Operations and Maintenance Manual
CODE DESCRIPTION EFFECT CORRECTION RESET
1
High Limit (STB)
Thermostat
activated
All burners
turned OFF and
Pump ON at
maximum speed.
Check FlowSensor thermal
connection to boiler.
reset switch
when
temperature goes
2
Low Gas
Pressure
All burners
turned OFF .
Check gas pressure or gas
pressure switch.
when gas
pressure switch
4
detected at
Burner control
lockout.
Check flame rod or
combustion.
reset switch or
5
Flame loss during
run.
Ignition retry.
Check combustion and
wiring.
reset switch or
6
temperature.
FlowSensor
temperature >
All burners
turned OFF and
Pump ON at
maximum speed.
Check Flow Sensor or
system pump
AUTOMATIC -
when
FlowSensor <
176°F.
10
Internal Failure
Contact Factory for new
BCM.
MANUAL - cycle
the power.
11
Flame signal
detected before
ignition.
Ignition is
inhibited.
Disconnect flame rod wire
from BMM. If problem
goes away change flame
rod and/or wire. If problem
does not go away change
MANUAL - push
reset switch or
cycle power.
12
FlowSensor fault.
Check flow sensor or
wiring.
AUTOMATIC
13
Aux Sensor fault
operate from the
FlowSensor
without the
Check aux sensor or
wiring.
AUTOMATIC
Table 10-4: BMM Fault Codes (Continued)