06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 110 of 112
Modulex E8 Controller and BCM
Operations and Maintenance Manual
15
temperature
protection.
Flow
temperature -
Return
Temperature >
Water Δ-Temp
Protection +
All burners
turned OFF
and Pump ON
at maximum
speed.
Check the system
installation.
AUTOMATIC -
when Δ-
temperature <
Water Δ-Temp
Protection.
16
frozen.
FlowSensor
temperature is
Ignition is
inhibited. Pump
runs for 5 min
at max speed.
Carefully defrost boiler
AUTOMATIC -
when FlowSensor
is greater than
41°F.
20
Flame signal
detected after
burner is OFF.
Ignition is
inhibited.
Disconnect gas valve wire
from BMM. If failure goes
away, check wiring or
change BMM. If failure
remains check or change
MANUAL - push
reset switch or
cycle power.
22
No air flow at
burner after fan
started for 30
seconds.
Ignition retry
after 60 second
delay and
failure remains
until we have a
successful
burner
operation.
supply voltage and fan
wiring. If OK try another
fan. If still not working
change the BMM.
If fan is not stopped, check
the exhaust gas outlet for
blockage. If OK then check
the air pressure switch
wiring. If still not working try
another air pressure switch.
If still not working, change
AUTOMATIC/MAN
UAL
23
The air
pressure switch
doesn't switch
off.
Ignition is
inhibited.
Disconnect the air proving
switch. If problem goes
away install a new switch. If
not, check the wiring. If
wiring OK then change
AUTOMATIC
Table 10-4: BMM Fault Codes (Continued)