MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
OMM-0087_0F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 109 of 146
GF-143 Phone: 800-526-0288 07/13/15
Table 5-6: EXPERT Menu - Continued
LEVEL DESCRIPTION ENTRY
INSTALLATION (Cont.) DEFAULT RANGE
IMODULAT MAX
If this modulation degree is exceeded, the next
heat .....
35 (10 - 60)
MODULAT MIN
If values drop this modulation degree, the last heat
35
(10 - 60)
MIN MOD HS
Connection of the next heat generator
35
(0 - 60)
MOD LEVEL HW
Entry of the set modulation degree for the heat
generators
80 (40 - 100)
SEQUENCE 1
Boiler sequence 1
12345678
SEQUENCE 2
Boiler sequence 2
87654321
SEQU CHANGE
Sequence change mode
06
(01 - 06)
SEQ SW TIME
Time to sequence change
200
(10 - 800)
LOCK TIME
Min. delay time after switching on or with switching
HS
01 (00 - 30)
HYST BURNER2
Solid fuel integration: hysteresys for the charging
pump
4 (3.6 – 36)Ra
HS COOL-FCT
Not used
0
(0 - 1)
T-HS COOL
Not used
176
(122 - 203)
HEATSOURCE 1
Primary heat generator type
06
(00 - 06)
HS 1 BUS
Connections for HS
02
(00 - 04)
HEATSOURCE 2
Secondary heat generator type
0
(00 - 05)
STORAGE HS 2
Heat accumulator for HS2
0
(00 - 03)
BUFFER
Heater buffer storage tank
0
(00 - 03)
SCREED
Activation of screed drying process
0
(00 - 01)
SCREED PROGR
Program setting
RETURN
HOT-WATER
DHW RELIEF
The charging pump is not switched until.....
0
(00 - 01)
PARALLEL
Pump parallel running
0
(00 - 03)
T-BOILER DHW
Boiler temperature setting with hot water
preparation
36 (00 - 90) Ra
HYST DHW
Hot water hysteresys
5
(9 - 54) Ra
DHW FOLLOWUP
Pump run-down time
0
(00 - 30)
THER INPUT
Storage tank with thermostat
0
(00 - 01)
WALL HUNG
Boiler temperature setting with hot water
preparation
0 (00 - 01)
LOAD THROUGH
The charge through function can be activated by...
0
(00 - 01)
RETURN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco MODULEX EXT 321 and is the answer not in the manual?

Aerco MODULEX EXT 321 Specifications

General IconGeneral
BrandAerco
ModelMODULEX EXT 321
CategoryBoiler
LanguageEnglish

Related product manuals