MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
OMM-0087_0F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 109 of 146
GF-143 Phone: 800-526-0288 07/13/15
Table 5-6: EXPERT Menu - Continued
LEVEL DESCRIPTION ENTRY
INSTALLATION (Cont.) DEFAULT RANGE
IMODULAT MAX
If this modulation degree is exceeded, the next
heat .....
35 (10 - 60)
If values drop this modulation degree, the last heat
Connection of the next heat generator
MOD LEVEL HW
Entry of the set modulation degree for the heat
generators
80 (40 - 100)
LOCK TIME
Min. delay time after switching on or with switching
HS
01 (00 - 30)
HYST BURNER2
Solid fuel integration: hysteresys for the charging
pump
4 (3.6 – 36)Ra
Primary heat generator type
Secondary heat generator type
Heater buffer storage tank
Activation of screed drying process
RETURN
HOT-WATER
The charging pump is not switched until.....
T-BOILER DHW
Boiler temperature setting with hot water
preparation
36 (00 - 90) Ra
Storage tank with thermostat
WALL HUNG
Boiler temperature setting with hot water
preparation
0 (00 - 01)
The charge through function can be activated by...
RETURN