EasyManuals Logo

AERMEC NRP 0280 User Manual

AERMEC NRP 0280
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
18 Aermec cod. 5806715_00 12.01
NRP 0200-0750
EN
8. OPERATIONAL LIMITS
Note:
1 In SUMMER mode, the unit can be started with
external air 46°C and inlet water 35°C.
In WINTER AND RECOVERY MODE, the unit
can be started with external air -15°C and inlet
water 20°C.
In these conditions, operation is only allowed for
a short amount of time and to bring the system to
the proper temperature.
To shorten this operation, it is recommended to
install a three-way valve which makes it possible
to bypass the water from the utilities to the plant,
until achieving conditions which allow the unit to
work within the allowed operating limits.
8.1. COOLING MODE¹
The units, in standard configuration, are not suitable
for installation in salty environments.
For functioning limits, please refer to the diagrams,
valid for t = 5°C.
8.2. HEATING MODE ¹
External air temperature d.b.°C
Produced water temperature EVAPORATOR°C
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
46
50
2345678
9
10 11 12 13 14 15 16
17 18 19
0
5
10
15
20
25
30
35
40
45
50
55
60
-15
-10
-5 0
20 25 30 35 40 45
10 15
42
External air temperature d.b.°C
Produced water temperature
CONDENSER °C
25
30
35
40
45
60
55
50
2345678
9
10 11 12 13 14 15 16
17 18 19
Produced water
temperature RECOVERY °C
Produced water temperature EVAPORATOR°C
ATTENTION
In windy areas, for correct operation
of DCPX it is recommended to install
a windbreak barrier.
It should be installed if wind velocity
is beyond 2.5 m/s.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC NRP 0280 and is the answer not in the manual?

AERMEC NRP 0280 Specifications

General IconGeneral
BrandAERMEC
ModelNRP 0280
CategoryHeat Pump
LanguageEnglish

Related product manuals