25Aermec cod. 5806715_00 12.01
NRP 0200-0750
EN
17. PARTIALISATIONS
Power steps
COOLING CAPACITY % 1
st
2
nd
3
rd
4
th
0200 55 100
0240 55 100
0280 55 100
0300 55 100
0330 55 100
0350 55 100
0500 40 75 100
0550 36 68 100
0600 25 50 75 100
0650 25 50 75 100
0700 25 50 75 100
0750 27 53 77 100
INPUT POWER % 1
st
2
nd
3
rd
4
th
0200 45 100
0240 45 100
0280 45 100
0300 45 100
0330 45 100
0350 45 100
0500 30 65 100
0550 26 58 100
0600 20 45 70 100
0650 20 45 70 100
0700 20 45 70 100
0750
23 47 73 100
HEATING CAPACITY % 1
st
2
nd
3
rd
4
th
0200 50 100
0240 50 100
0280 50 100
0300 50 100
0330 50 100
0350 50 100
0500 35 70 100
0550 31 63 100
0600 23 48 73 100
0650 23 48 73 100
0700 23 48 73 100
0750 27 52 73 100
INPUT POWER % 1
st
2
nd
3
rd
4
th
0200 45 100
0240 45 100
0280 45 100
0300 45 100
0330 45 100
0350 45 100
0500 30 65 100
0550 26 58 100
0600 20 45 70 100
0650 20 45 70 100
0700 20 45 70 100
0750 23 47 73 100
COOLING
Evaporator inlet water temperature 7°C
Evaporator outlet water temperature 12°C
Condenser air temperature 35°C
Δt water 5°C
HEATING ONLY FOR 4-PIPE VERSIONS ????
Condenser inlet water temperature 40°C
Condenser outlet water temperature 45°C
Evaporator air temperature 7°C d.b. 6°C w.b.
Δt water 5°C