26 Aermec cod. 5806715_00 12.01
NRP 0200-0750
EN
18. SOUND DATA
NRP
VERS
Total sound levels Octave band [Hz]
Pow.
dB(A)
Pressure. 125 250 500 1000 2000 4000 8000
dB(A)
10 m
dB(A)
1 m
Sound potential for central band [dB] (A) frequency
COOLING MODE FUNCTIONING
0200 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0240 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0280 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0300 HE
75 43 57 73.1 62.2 67.1 64.3 62.0 51.0 44.5
0330 HE
75 43 57 73.1 62.0 67.1 64.3 62.1 51.3 44.8
0350 HE
76 44 58 74.1 63.0 68.1 65.6 62.6 53.0 45.1
0500 HE
74 42 56 60.9 63.9 66.9 68.8 67.1 63.3 56.9
0550 HE
74 42 56 61.4 64.6 68.1 68.8 67.2 63.3 56.9
0600 HE
74 42 56 61.6 65.1 68.2 68.9 67.2 63.5 57.4
0650 HE
75 43 57 62.1 65.1 68.5 69.1 68.4 65.5 61.5
0700 HE
77 45 58 65.7 67.6 68.6 69.8 71.4 65.7 62.0
0750 HE
77 45 58 65.9 67.9 68.8 69.8 71.2 65.5 61.9
0500 HA
82 50 64 68.1 69.8 74.0 76.7 76.5 74.1 63.8
0550 HA
82 50 64 68.1 69.9 75.0 77.5 76.5 72.0 61.0
0600 HA
82 50 64 68.9 71.4 74.8 77.7 76.4 72.0 59.9
0650 HA
83 51 65 69.4 70.6 75.1 77.9 78.0 74.6 64.1
0700 HA
85 53 66 72.9 73.2 78.0 78.3 80.0 76.6 65.2
0750 HA
85 53 66 72.8 73.3 78.1 78.5 80.0 76.2 65.2
FUNCTIONING IN HEATING MODE
0200 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0240 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0280 HE
74 42 57 72.2 61.1 66.4 63.5 61.0 50.0 43.7
0300 HE
75 43 57 73.1 62.2 67.1 64.3 62.0 51.0 44.5
0330 HE
75 43 57 73.1 62.0 67.1 64.3 62.1 51.3 44.8
0350 HE
76 44 58 74.1 63.0 68.1 65.6 62.6 53.0 45.1
0500 HE
82 50 64 68.1 69.8 74.0 76.7 76.5 74.1 63.8
0550 HE
82 50 64 68.1 69.9 75.0 77.5 76.5 72.0 61.0
0600 HE
82 50 64 68.9 71.4 74.8 77.7 76.4 72.0 59.9
0650 HE
83 51 65 69.4 70.6 75.1 77.9 78.0 74.6 64.1
0700 HE
85 53 66 72.9 73.2 78.0 78.3 80.0 76.6 65.2
0750 HE
85 53 66 72.8 73.3 78.1 78.5 80.0 76.2 65.2
0500 HA
82 50 64 68.1 69.8 74.0 76.7 76.5 74.1 63.8
0550 HA
82 50 64 68.1 69.9 75.0 77.5 76.5 72.0 61.0
0600 HA
82 50 64 68.9 71.4 74.8 77.7 76.4 72.0 59.9
0650 HA
83 51 65 69.4 70.6 75.1 77.9 78.0 74.6 64.1
0700 HA
85 53 66 72.9 73.2 78.0 78.3 80.0 76.6 65.2
0750 HA
85 53 66 72.8 73.3 78.1 78.5 80.0 76.2 65.2
ATTENTION
The sound data is calculated with
STANDARD fans!
Sound power
Aermec determines sound power values
in agreement with the 9614-2 Standard, in
compliance with that requested by Eurovent
certification.
Sound pressure
Sound pressure measured in free field conditions
with reflective surface (directivity factor Q=2) in
compliance with ISO 3744 Standard.
Cooling mode – The ‘HE’ version is low noise with
temperature 12/7°C -35°C
Heating mode – The ‘HE’ version is low noise
witth temperature > 25°