19. CALIBRATIONS OF SAFETY AND CONTROL PARAMETERS
COOLING SET min max default
Water inlet temperature (cooling mode) -10°C 20°C 7°C
HEATING SET
Water inlet temperature (heating mode)
30°C 55°C 50°C
ANTI-FREEZE ALARM INTERVENTION
Intervention temperature on EVAPORATOR side
-15°C 4°C 3°C
TOTAL DIFFERENTIAL
Proportional temperature band within which the
compressors are activated and deactivated
3°C 10°C 5°C
COMPRESSOR MAGNET
CIRCUIT BREAKERS
0200 0240 0280 0300 0330 0350 0500 0550 0600 0650 0700 0750
MTC1
A 171723282829232828282929
MTC1A
A - - - - - - 23 23 23 28 29 29
MTC2 A 172323232829282928282940
MTC2A A - - - - - - 23 28 29 40
MANUALLY RESET HIGH PRESSURE SWITCH
PA bar
40 40 40 40 40 40 40 40 40 40 40 40
HIGH PRESSURE TRANSDUCER
TAP bar 39 39 39 39 39 39 39 39 39 39 39 39
LOW PRESSURE TRANSDUCER
TBP bar222222222222
COOLING CIRCUIT SAFETY VALVES
HP bar 45 45 45 45 45 45 45 45 45 45 45 45
LP bar 30 30 30 30 30 30 30 30 30 30 30 30
MAGNETOTHERMIC FANS
HE VERSIONS A 4 4 6 8 8 8 2 2 2 2 3 14