EasyManua.ls Logo

Alber BDS-40 - Base to Plus Unit Fiber Optic Connection; Figure 44. Snapshot BDS-1193-B986; Figure 45. Base to Plus Unit Connection

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Begin System Installation
4200045
32
6/5/2017
Connection can be made directly to a facility's alarm reporting system. If there is more than one
BDS at the same location and only one set of contacts can be monitored, the alarm contacts
can be wired in parallel. Refer to BDS1193B986.
The plus and minus remote reset input contacts are on the BDS40 Base Unit rear panel.
Connecting a +12VDC/GND signal to the reset input contacts will reset alarms for all strings. If
there is more than one BDS at the same location, and only one set of contacts is available for
reset, these inputs can be wired in parallel.
NOTE:
The ground connection is the most right connection in the 8 eight position connector.
Figure 44. Snapshot BDS1193B986
7.3 Base To Plus Unit Fiber Optic Connection
When using a BDS40 Base unit with one or more BDS40 Plus units, connect the Base and
Plus units as shown in the following figure. Use Application Details Drawing BDS5274B1054
as an example.
Figure 45. Base to Plus Unit Connection

Table of Contents