160 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix C Configuration Reference Information
Table 69 - Test Output Parameters
Parameter Name Value Description Default
Test Output Mode Not Used An external device is not connected. Not Used
Standard The output is connected to a standard device.
Pulse Test A contact output device is connected. Use in combination with a safety
input.
Power Supply The power supply of a Safety Sensor is connected. The voltage supplied to
I/O power (V, G) is output from the test output terminal.
Muting Lamp Output
1791ES-IB8XOBV4, 1732ES-IB8XOBV4,
1732ES-IB8XOB8 modules = T3 and T7
1791ES-IB16, 1732ES-IB16 modules = T3, T7,
T11, and T15
1732ES-IB12XOBV2, 1732ES-IB12XOB4
modules = T3, T7, and T11
An indicator is connected and turned ON to detect broken lines in an
external indicator.
Table 70 - Safety Output Parameters
Parameter Name Value Description Default
Output Point Mode Not Used An external output device is not connected. Not Used
Safety When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test By using this function, short circuits between output signal lines and the
power supply (positive side) and short circuits between output signal lines
can be detected.
Output Point Operation Type Single Channel
(1)
Use as single channel. Dual-channel
Dual-channel Use as dual-channel. When both channels are normal, outputs can be
turned ON.
(1) 1732ES-IB12XOB4 and 1732ES-IB8XOB8 modules only.