Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016 95
Replace Guard I/O Modules Chapter 6
Figure 33 - Safety I/O Replacement Options
Configure Only When No Safety Signature Exists
This setting instructs the GuardLogix controller to configure a safety device
only when the safety task does not have a safety task signature. The
replacement device must also be in an out-of-box condition, meaning that a
safety network number does not exist in the safety device.
If the safety task has a safety task signature, the GuardLogix controller only
automatically configures the replacement CIP Safety I/O device if the
following is true:
The device already has the correct safety network number.
The device electronic keying is correct.
The node or IP address is correct.
For detailed information, see the appropriate GuardLogix Safety Reference
Manual, which is listed in the Additional Resources on page 10
.
Configure Always
The GuardLogix controller always attempts to configure a replacement CIP
Safety I/O device if the device is in an out-of-box condition. This occurrence
means that a safety network number does not exist in the replacement safety
device and the node number and I/O device keying matches the configuration
of the controller.