46 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Chapter 3 Install the Module
Module Spacing
Leave minimum spacing to the wiring duct or other objects for adequate
ventilation and room for wiring.
Figure 18 - Required Spacing for 1791ES-IB16 and 1791ES-IB8XOBV4 Modules
Wiring Duct or Other Object
15 mm (0.6 in.) Min
35 mm (1.38 in.) DIN Rail
Use horizontal or
vertical mounting.
End Plate
Wiring Duct or Other Object
15 mm (0.6 in.) Min
End Plate