Rockwell Automation Publication 193-QR004B-EN-P - January 2017 37
Appendix A
E300 Relay Operating Mode Summary
This section summarizes the preset configurations for the various E300 relay Operating Modes that can be selected using
the ConfigPreset (Parameter 164) command.
Detailed information about the E300 relay Operating Modes is found in Chapter 5 of the E300 Electronic Overload
Re
lay User Manual, publication
193-UM015.
The default Operating Mode is (2) - Network Overload. The four most common Operating Modes are:
(2) - Network Overload
(4) - Network Non-Reversing Starter
(11)
- Network & Operator Station Non-Reversing Starter
(16) - Network & Local I/O 2-Wire Control Non-Reversing Starter
Table 1 - E300 Relay Preset Configurations (Parameter 164)
Value Enumeration
Operating Mode
Description
Control
Sou
rce
Starter Type Control Option
0 Ready No operation
1 FactoryDefaults Set all parameters to their default setting
2 NetOverload Network Overload A controller is the control source for a traditional overload relay with a trip contact
3 NetNonRev2Wire Network Non-reversing A controller is the control source for a non-reversing starter that has a maintained signal
4 NetNonRevFB2Wire Network Non-reversing
With Feedback
Pr
otection
A controller is the control source for a non-reversing starter that has a maintained signal, and
the E300 relay will trip if the contactor auxiliary is not closed
5 NetRev2Wire Network Reversing A controller is the control source for a reversing starter that has a maintained signal
6 NetRevFB2Wire Network Reversing
With Feedback
Prot
ection
A controller is the control source for a reversing starter that has a maintained signal, and the
E300 relay will trip if the contactor auxiliary is not closed
7 NetOpWyeDelta2W Network Wye/Delta Open Transition
A controller is the control source for a Wye/Delta starter that has a maintained signal and has
an open t
ransition
8 NetClWyeDelta2W Network Wye/Delta Closed Transition
A controller is the control source for a Wye/Delta starter that has a maintained signal and has a
closed
transition
9 Net2Speed2Wire Network 2-Speed A controller is the control source for a 2-Speed starter that has a maintained signal
10 Net2SpeedFB2Wire Network 2-Speed
With Feedback
Prot
ection
A controller is the control source for a 2-Speed starter that has a maintained signal, and the
E300 relay will trip if the contactor auxiliary is not closed
11 NetOSNonRev3Wir
Network &
Op
erator
Station
Non-reversing
A controller that has a maintained signal and an Operator Station with momentary control
buttons are the control sources for a non-reversing starter
12 NetOSNonRevFB3W
Network &
Op
erator
Station
Non-reversing
With Feedback
Protection
A controller that has a maintained signal and an Operator Station with momentary control
buttons are the control sources for a non-reversing starter, and the E300 relay will trip if the
contactor auxiliary is not closed
13 NetOSRev3Wire
Network &
Operator
Station
Reversing
A controller that has a maintained signal and an Operator Station with momentary control
buttons are the control sources for a reversing starter
14 NetOSOpWyeDel3W
Network &
Op
erator
Station
Wye/Delta Open Transition
A controller that has a maintained signal and an Operator Station with momentary control
buttons are the control sources for a Wye/Delta starter that has an open transition
15 NetOS2Speed3Wir
Network &
Op
erator
Station
2-Speed
A controller that has a maintained signal and an Operator Station with momentary control
buttons are the control sources for a 2-speed starter