38 Rockwell Automation Publication 193-QR004B-EN-P - January 2017
Appendix A
16 NetLIONonRev2Wir
Network &
Local I/O
Non-reversing 2 Wire Control
A controller that has a maintained signal and a maintained selector switch are the control
sources for a non-reversing starter
17 NetLIONonRevFB2W
Network &
Loc
al I/O
Non-reversing
2 Wire Control with
Feedback Protection
A controller that has a maintained signal and a maintained selector switch are the control
sources for a non-reversing starter, and the E300 relay will trip if the contactor auxiliary is not
closed of the contactor
18 NetLIONonRev3Wir
Network &
Loc
al I/O
Non-reversing 3 Wire Control
A controller that has a maintained signal and two momentary push buttons are the control
sources for a non-reversing starter
19 NetLIONonRevFB3W
Network &
Loc
al I/O
Non-reversing
3 Wire Control with
Feedback Protection
A controller that has a maintained signal and two momentary push buttons are the control
sources for a non-reversing starter, and the E300 relay will trip if the contactor auxiliary is not
closed of the contactor
20 NetLIORev2Wire
Network &
Local I/O
Reversing 2 Wire Control
A controller that has a maintained signal and a maintained selector switch are the control
sources for a reversing starter
21 NetLIORev3Wire
Network &
Loc
al I/O
Reversing 3 Wire Control
A controller that has a maintained signal and three momentary push buttons are the control
sources for a reversing starter
22 NetLIOOpWyeDel2W
Network &
Loc
al I/O
Wye/Delta
2 Wire Control with
Open Transition
A controller that has a maintained signal and a maintained selector switch are the control
sources for a wye/delta starter with an open transition
23 NetLIOClWyeDel2W
Network &
Local I/O
Wye/Delta
2 Wire Control with
Closed Transition
A controller that has a maintained signal and a maintained selector switch are the control
sources for a wye/delta starter with a closed transition
24 NetLIO2Speed2Wir
Network &
Loc
al I/O
2-Speed 2 Wire Control
A controller that has a maintained signal and a maintained selector switch are the control
sources for a 2-speed starter
25 NetLIO2Speed3Wir
Network &
Loc
al I/O
2-Speed 3 Wire Control
A controller that has a maintained signal and three momentary push buttons are the control
sources for a 2-speed starter
26 OSOverload
Operator
Station
Overload
An Operator Station with a momentary trip reset button is the control source for a traditional
overload relay with a trip contact
27 OSNonRev3Wire
Operator
Stat
ion
Non-reversing
An Operator Station with momentary control buttons is the control source for a non-reversing
starter
28 OSNonRevFB3Wire
Operator
Stat
ion
Non-reversing
With Feedback
Protection
An Operator Station with momentary control buttons is the control source for a non-reversing
starter, and the E300 relay will trip if the contactor auxiliary is not closed of the contactor
29 OSRev3Wire
Operator
Station
Reversing
An Operator Station with momentary control buttons is the control source for a reversing
starter
30 OSRevFB3Wire
Operator
Stat
ion
Reversing
With Feedback
Protection
An Operator Station with momentary control buttons is the control source for a reversing
starter, and the E300 relay will trip if the contactor auxiliary is not closed
31 OSOpWyeDel3W
Operator
Stat
ion
Wye/Delta Open Transition
An Operator Station with momentary control buttons is the control source for a wye/delta
starter with an open transition
32 OSClWyeDelta3W
Operator
Station
Wye/Delta Closed Transition
An Operator Station with momentary control buttons is the control source for a wye/delta
starter with a closed transition
33 OS2Speed3Wire
Operator
Stat
ion
2-Speed
An Operator Station with momentary control buttons is the control source for a 2-speed
starter
34 OS2SpeedFB3Wire
Operator
Stat
ion
2-Speed
With Feedback
Protection
An Operator Station with momentary control buttons is the control source for a 2-speed
starter, and the E300 relay will trip if the contactor auxiliary is not closed
35 LIOOverload Local I/O Overload
A momentary push button for a trip reset is the control source for a traditional overload relay
with a trip contact
36 LIONonRev2Wire Local I/O Non-reversing 2 Wire Control A maintained selector switch is the control source for a non-reversing starter
37 LIONonRevFB2Wire Local I/O Non-reversing
2 Wire Control with
F
e
edback Protection
A maintained selector switch is the control sources for a non-reversing starter, and the E300
relay will trip if the contactor auxiliary is not closed of the contactor
38 LIONonRev3Wire Local I/O Non-reversing 3 Wire Control Two momentary push buttons are the control sources for a non-reversing starter
39
LIONonRevFB3Wire Local I/O Non-reversing
3 Wire Control with
Feedback Protection
Three momentary push buttons are the control sources for a non-reversing starter, and the
E300 relay will trip if the contactor auxiliary is not closed of the contactor
40 LIORev2Wire Local I/O Reversing 2 Wire Control A maintained selector switch is the control source for a reversing starter
41 LIORevFB2Wire Local I/O Reversing
2 Wire Control with
F
e
edback Protection
A maintained selector switch is the control source for a reversing starter, and the E300 relay
will trip if the contactor auxiliary is not closed of the contactor
42 LIORev3Wire Local I/O Reversing 3 Wire Control Three momentary push buttons are the control sources for a reversing starter
43 LIOOpWyeDelta2W Local I/O Wye/Delta
2 Wire Control with
Open Tr
ansition
A selector switch is the control source for a wye/delta starter with an open transition
Table 1 - E300 Relay Preset Configurations (Parameter 164)
Value Enumeration
Operating Mode
Description
Control
Source
Starter Type Control Option