3-22 Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group (continued)
A419 [Skip Freq Band] Related Parameter(s): A418
Determines the bandwidth around A418 [Skip Frequency]. A419 [Skip Freq Band] is applied above
and below the actual skip frequency. See the diagram below.
A setting of 0.0 disables this parameter.
Values Default: 0.0 Hz
Min/Max: 0.0/30.0 Hz
Display: 0.1 Hz
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
A424 [DC Brake Time] Related Parameter(s): P107, A425
Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter A425 [DC
Brake Level].
Values Default 0.0 Secs
Min/Max: 0.0/99.9 Secs (A setting of 99.9 = Continuous)
Display: 0.1 Secs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 4M and is the answer not in the manual?

Allen-Bradley PowerFlex 4M Specifications

General IconGeneral
Input Voltage200…240V AC, 380…480V AC, 500…600V AC
Output Voltage0-Input Voltage
Control MethodSensorless Vector
CommunicationsRS-485
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
EnclosureIP20
Operating Temperature-10°C to 50°C
Storage Temperature-40°C to 70°C
Humidity5-95% (non-condensing)
DimensionsVaries by model
WeightVaries by model