70 Rockwell Automation Publication 20A-UM001N-EN-P - July 2013
Chapter 1 Programming and Parameters
INPUTS and OUTPUTS (file J)
Digital Outputs
380
384
[Digital Out1 Sel]
[Digital Out2 Sel]
Selects the drive status that energizes a (CRx)
output relay.
(1)
Any relay programmed as Fault or Alarm energizes
(pick up) when power is applied to drive and
deenergize (drop out) when a fault or alarm exists.
Relays selected for other functions energizes when
that condition exists and deenergize when condition
is removed.
Refer to I/O Wiring Examples in the
PowerFlex 70 Adjustable Frequency AC Drive Installation
Instructions, publication 20A-IN009.
(2)
Activation level is defined in [Dig Outx Level] below.
(3)
Only Enhanced Control Drives.
(4)
Enhanced firmware revision V3.002 and later.
(5)
Enhanced firmware revision V4.001 and later.
Default:
Options:
1
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31…57
58
59
60
61
“Fault”
“Run”
“Fault”
(1)
“A la rm
(1)
“Ready”
“Run”
“Forward Run
“Reverse Run”
Auto Restart”
“Powerup Run
“At Speed
“At Freq
(2)
“At Current
(2)
“At Torque
(2)
“At Temp
(2)
“At Bus Volts
(2)
“At PI Error
(2)
“DC Braking”
“Curr Limit”
“Economize
“Motor Overld”
“Power Loss”
“Input 1 Link”
“Input 2 Link”
“Input 3 Link”
“Input 4 Link”
“Input 5 Link”
“Input 6 Link”
“PI Enabled”
(3)
“PI Hold”
(3)
“Drive Overld”
(3)
“Param Cntl”
(3)
“Reserved”
“Manual Mode”
(4)
“Fast Braking”
(4)
“Reserved”
“Speed Fdbk”
(2)(5)
381
382
383
002
001
003
004
218
012
137
157
147
053
048
184
381
385
[Dig Out1 Level]
[Dig Out2 Level]
Sets the relay activation level for options 10 – 15
in [Digital Outx Sel]. Units are assumed to match
the above selection (for example, “At Freq” = Hz,
At Torque” = Amps).
Default:
Min/Max:
Units:
0.0
0.0
0.0/819.2
0.1
380
382
386
[Dig Out1 OnTime]
[Dig Out2 OnTime]
Sets the “ON Delay” time for the digital outputs.
This is the time between the occurrence of a
condition and activation of the relay.
Default:
Min/Max:
Units:
0.0 Secs
0.0 Secs
0.0/600.0 Secs
0.1 Secs
380
383
387
[Dig Out1 OffTime]
[Dig Out2 OffTime]
Sets the “OFF Delay” time for the digital outputs.
This is the time between the disappearance of a
condition and de-activation of the relay.
Default:
Min/Max:
Units:
0.0 Secs
0.0 Secs
0.0/600.0 Secs
0.1 Secs
380
File J
Group
No.
Parameter Name and Description
See page 14 for symbol descriptions
Values
Related

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
Frequency Range0 - 400 Hz
Humidity5% to 95% non-condensing
Output Voltage0 to Input Voltage
Control MethodsSensorless Vector Control
CommunicationsEthernet/IP, DeviceNet, ControlNet
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Ground Fault
Operating Temperature0°C to 50°C (32°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Enclosure RatingIP20, NEMA Type 1