Store Pump Cycle Torque
1. Verif y the well is f ull.
2. Enter a command speed.
3. Start the Pump Jack from the HIM.
4. Set P1192 [Pump Cycle Store] to option 1 “Enable.
If the Pump Off feature detects a pump jack torque-signature waveform,
the waveform is stored and the parameter resets to 0 “Disabled.
If this parameter does not reset to 0 “Disabled,” set P1187 [Pump Off
Config] to option 2 “Cycle.” In Cycle mode, the entire cycle torque is used
as the down-stroke torque used in the original pump off detection. There is
no need to set the top of stroke in this mode.
Initialize Pump Stroke Position
1. Set P1193 [Set Top ofStroke] to option 1 “Enable.
Use a Human Interface Module (HIM) to avoid any communication
delays.
2. Press enter when you visually see the Horsehead at the top position. This
action sets the stroke position to the stored pump cycle torque.
3. Stop the drive.
4. Configure DriveObserver with the following parameters.
P5 [Torque Cur Fdbk]
P972 [Testpoint Lval]
P1198 [Pct Cycle Torque]
P1200 [Pct Drop Torque]
P1201 [Stroke Pos Count]

Table of Contents

Other manuals for Allen-Bradley PowerFlex 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 750 Series and is the answer not in the manual?

Allen-Bradley PowerFlex 750 Series Specifications

General IconGeneral
CategoryController
SeriesPowerFlex 750 Series
DimensionsVaries by model
WeightVaries by model
Output Voltage Range0V to Input Voltage
Output Frequency Range0 to 400 Hz
Control MethodVector Control
Communication ProtocolsEtherNet/IP, DeviceNet, ControlNet
Enclosure TypesNEMA 1, NEMA 12, NEMA 4X, IP20
SafetySafe Torque Off (STO)
Ambient Operating Temperature0 to 40 °C (32 to 104 °F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Relative Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280 ft) without derating

Related product manuals