EasyManuals Logo

Allen-Bradley PowerFlex 750 Series Programming Manual

Allen-Bradley PowerFlex 750 Series
548 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #493 background imageLoading...
Page #493 background image
Rockwell Automation Publication 750-PM001N-EN-P - February 2017 493
Using DeviceLogix Appendix D
Example logic requirements:
• If Critical High-Level or High-Level sensor is ON, then start the drive.
– If Critical High-Level sensor is ON, then switch to higher rate (90 Hz)
for the rest of the pumping cycle. Else run at the normal rate (60 Hz)
– Run until all three level sensors are OFF
– Pump should run at least ‘x’ minutes at a minimum. If the Low-Level
sensor fails, this prevents the High-Level sensor from cycling the pump
On/Off too quickly.
• Annunciate a Sensor Fault condition
– The Low-Level sensor should never be OFF when either the High
Level or Critical High-Level sensors are ON
– The High-Level sensor should never be OFF when the Critical High-
Level sensor is ON
– The Critical High-Level sensor should never be ON when either the
High-Level or Low-Level sensors are OFF
• Annunciate a Critical High-Level condition
– The Critical High-Level output should never be ON
• Annunciate if pumping cycle time is longer than normal (‘y’ minutes)
– Monitor the amount of time a pump cycle takes by timing how long the
drive is operating.
– If greater than ‘y’ minutes, energize the Too Much Time Alarm output
• Reset alarms / faults with a Reset pushbutton input
Parameter Configuration
The following parameters are configured for this example.
The following DeviceLogix parameters are configured for this example:
Port Parameter
No.
Parameter Value Description
0.520 Max Fwd Speed 90.00
0.545 Speed Ref A Sel Port 0: Preset Speed 1
0.571 Preset Speed 1 60.00 Normal pumping rate (60 Hz)
0.573 Preset Speed 3 90.00 High speed pumping rate (90 Hz)
4.10 RO0 Select Port 14: DLX DigOut Sts2.DLX
DOPSts0
Sensor Fault output
4.20 TO0 Select Port 14: DLX DigOut Sts2.DLX
DOPSts1
Critical High-Level Fault output
4.30 TO1 Select Port 14: DLX DigOut Sts2.DLX
DOPSts2
Too Much Time Alarm output
14.33 DLX DIP 1 Port 4: Dig In Status.Input 1 Critical High-Level Sensor input
14.34 DLX DIP 2 Port 4: Dig In Status.Input 2 High-Level Sensor input
14.35 DLX DIP 3 Port 4: Dig In Status.Input 3 Low-Level Sensor input
14.36 DLX DIP 4 Port 4: Dig In Status.Input 4 Alarm / Fault Reset pushbutton
input

Table of Contents

Other manuals for Allen-Bradley PowerFlex 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 750 Series and is the answer not in the manual?

Allen-Bradley PowerFlex 750 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 750 Series
CategoryController
LanguageEnglish

Related product manuals