Appendix D Using DeviceLogix
Parameter Configuration
The following parameters are configured for this example:
Functional Block Programming
This example consists of 15 blocks that are shown in the following figure.
Port Parameter
No.
Parameter Value Description
0.545 Speed Ref A Sel Port 0: Preset Speed 1
0.571 Preset Speed 1 60.00 Operating speed of drive
Hour
9
Minute
13
Day Of Week
0
1 GEQ
Grtr Than or
Eql (A>=B)
EnableIn
SourceA
SourceB
1
1
2 LEQ
Less Than or
Eql (A<=B)
EnableIn
SourceA
SourceB
1
1
3 BAND
Boolean And
EnableIn
In1
In2
1
1
4 GEQ
Grtr Than or
Eql (A>=B)
EnableIn
SourceA
SourceB
1
1
7 EQU
Equal
EnableIn
SourceA
SourceB
1
0
8 GEQ
Grtr Than or
Eql (A>=B)
EnableIn
SourceA
SourceB
1
0
9 BAND
Boolean And
EnableIn
In1
In2
1
0
10 EQU
Equal
EnableIn
SourceA
SourceB
1
0
12 BAND
Boolean And
EnableIn
In1
In2
1
0
13 BOR
Boolean Or
EnableIn
In1
In2
In3
1
1
Stop
0
Start
1
Forward
1
SpdRef Sel 0
1
Monday - Fri day
8:00 - 16:59
7:45 - 7:59
17:00 - 17:14
5 LES
Less Than (A<B)
EnableIn
SourceA
SourceB
1
1
6 BAND
Boolean And
EnableIn
In1
In2
1
1
14 BAND
Boolean And
EnableIn
In1
In2
1
1
15 PULR
Pulse Timer with Reset
EnableIn
TimerEnable
Reset
1
0
11 LES
Less Than (A<B)
EnableIn
SourceA
SourceB
1
1