18 Rockwell Automation Publication 1783-UM010C-EN-P - June 2019
Chapter 1 About the Security Appliance
Management Ethernet Port
A management-only 10/100/1000 BaseT Ethernet port is provided. This port
is the only port that is able to configure the device for initial setup of the
system. This port is Management1/1 in the ASA configuration.
Console Port
You can configure the Stratix 5950 security appliance through a web interface,
or through the console port. The console port is either an RJ45 or a Mini USB
connector. You can use the Rockwell Automation USB to RJ45 console cable
(part number 9300-USBCBL-CNSL).
The default configuration settings for the RJ45 console port are:
9600 baud, 8 data bits, no parity, 1 stop bit, no flow control.
If the USB Console Port is active, by default, the console switches from RJ45
to USB when the USB cable is detected. The USB Console Port is active when
a cable is inserted and remote personal computer drivers are enabled. When
both ports are connected, the Mini USB console port is used.
This table shows the pinouts for the CON/AUX RJ45 connector.
Table 3 - Pinouts for the CON/AUX RJ45 Connector
Pin Signal Direction
1DTR Output
23.3 Output
3TXD Output
4GND
5GND
6RXD Input
7- NC
8- NC
IMPORTANT The console port does not support a remote dial-in modem.