Configure a ControlNet Module 
 
  Rockwell Automation Publication CNET-UM001F-EN-P - February 2018  37 
•  What tags are generated when configuration is complete 
•  The type of connection between the owner-controller and the I/O 
connected via the communication module 
The communication format setting also affects the RPI rate. 
Table 7 - Communication Formats 
Communication Format  Function  Effect on RPI 
Rack-optimized  The communication module creates a rack 
image and returns I/O data in the rack image to 
the owner-controller. 
This option is available only for digital I/O 
modules. Remember that diagnostic I/O 
modules will not return diagnostic data when 
you use this format. 
You can specify an RPI that meets this criteria: 
•  Equal to or greater than the NUT 
•  In the range permitted by Logix Designer 
programming software, for example 2…750 
ms 
When you set the RPI for a remote ControlNet 
communication module, we recommend you 
use a rate that is a power of two times the NUT. 
For example, if your NUT = 5 ms, we 
recommend these RPI values. 
Listen-only rack-
optimized (not available 
on all ControlNet 
communication modules) 
The communication module creates a rack 
image and returns I/O input data in the rack 
image to the owner-controller. 
The difference between this choice and rack-
optimized is that the I/O data in the rack image 
is returned to a controller that does not control 
the outputs but is listening only to its input data. 
None  No RPI is required.  The RPI field is dimmed. 
4.  On the Module Properties dialog box, configure the connection 
properties and then click Apply. 
Connection Property  Action 
Requested Packet Interval (RPI)  Type the requested packet interval between 2.0…750.0 ms. 
If your module uses one of the rack-optimized communication formats, the 
RPI must be equal to or greater than the ControlNet Network Update Time 
(NUT). 
Inhibit Module 
If the module does not need to communicate with the controller, check the 
checkbox. 
or 
If the module needs to communicate with the controller, leave the checkbox 
cleared. 
IMPORTANT: When you test this portion of the system, leave the checkbox 
cleared. 
Major Fault On Controller If Connection Fails 
While In Run Mode 
If you want the controller to produce a major fault if the connection to the 
local communication module fails in Run mode, check the checkbox. 
or 
If you want the controller to continue operating if the connection to the local 
communication module fails in Run mode, leave the checkbox cleared. Use 
ladder logic to monitor the connection.