Configure a ControlNet Module 
 
  Rockwell Automation Publication CNET-UM001F-EN-P - February 2018  41 
Important: 
Changing Electronic Keying parameters online interrupts connections to the device 
and any devices that are connected through the device. Connections from other 
controllers can also be broken. 
If an I/O connection to a device is interrupted, the result can be a loss of data.  
 
Exact Match keying requires all keying attributes, that is, Vendor, Product 
Type, Product Code (catalog number), Major Revision, and Minor Revision, 
of the physical module and the module created in the software to match 
precisely in order to establish communication. If any attribute does not match 
precisely, I/O communication is not permitted with the module or with 
modules connected through it, as in the case of a communication module. 
Use Exact Match keying when you need the system to verify that the module 
revisions in use are exactly as specified in the project, such as for use in 
highly-regulated industries. Exact Match keying is also necessary to enable 
Automatic Firmware Update for the module via the Firmware Supervisor 
feature from a Logix 5000 controller.