22  Rockwell Automation Publication CNET-UM001F-EN-P - February 2018 
The UMAX is the highest network address of a node that can 
communicate on a ControlNet network. The UMAX must be set equal 
to or higher than the SMAX. 
•  Assumed maximum cable lengths and maximum number of repeaters 
With this default ControlNet network, you can have unscheduled 
communication between the various devices on the network by using Logix 
Designer application and RSLinx software. 
Important: 
To improve performance, configure a ControlNet network with RSNetWorx for ControlNet software. We 
recommend these settings: 
•  Set the Unscheduled Maximum Node Address (UMAX) equal to the highest node address on the network. 
Leaving this parameter at the default value of 99 wastes bandwidth    and reduces system performance. 
•  Set the Scheduled Maximum Node Address (SMAX) to a value three or four above the highest scheduled 
node address, so you can expand the network in the future. 
Also, be aware that each skipped node will subtract a small amount of bandwidth from the network. 
 
When planning a ControlNet network, consider these factors: 
•  Topology 
•  Number of nodes 
•  Distances 
•  Connections 
A ControlNet network supports a variety of topologies, including 
trunkline/dropline, star, tree, and ring redundancy. In its simplest form, a 
ControlNet network is a trunkline to which you connect nodes with a tap and 
a one-meter dropline. 
Figure 5 - Example ControlNet Network Trunkline/Dropline Topology 
 
Item  Description 
Trunkline 
Node 
Tap with dropline 
Capacity and 
Topology