Chapter 4 Parameter Index
51
P1: Start-stop control
Function
code
Parameter LCD display Setting range Factory setting Mod.
MODBUS
address
P1.00 Starting mode Starting mode
0: Start from the start
frequency
1: First brake (excitation),
and then start at the start
frequency
2: Rotating speed
tracking (must be
connected to PG or
rotating speed tracking
board, 3004GB and below
models do not support
rotating speed tracking
board)
Note: The startup procedure
includes initial power-on,
power restoration after
instantaneous stop, external
fault reset, and all startup
procedure after free stopping
0 ○ 0200
P1.01
Starting
frequency
Starting
frequency
0.10~60.00Hz 0.50Hz ○ 0201
P1.02
Starting
frequency hold
time
Start hold time 0.0~10.0s 0.0s ○ 0202
P1.03
Start DC
braking current
Start braking
current
Depend on model
0-100.0% of rated current of
the motor.
It is active only in V/F
control mode, the upper limit
is 80% of the nominal current
of inverter or smaller one
among the nominal current of
the motor; in vector control
mode, the current is
determined by P8.00
pre-excitation current
compensation factor; when
the set value is less than
100%, perform it at 100%
0.0% ○ 0203
P1.04
Start DC
braking time
Start braking
time
0.0~30.0s 0.1s ○ 0204
P1.05
Start preset
frequency
Start preset
frequency
0.00-maximum frequency 0.00Hz × 0205
P1.06
Preset
frequency hold
time
Preset
frequency hold
time
0.0~3600.0s 0.0s × 0206
P1.07
Acceleration
and
deceleration
mode
Acceleration
and
deceleration
mode
0: Linear 1: S curve
2: (Reserve) 3: (Reserve)
0 ○ 0207
P1.08
S curve start
time
S curve start
segment
10.0-50.0 % (acceleration and
deceleration time )
P1.08+P1.09≤90%
20.0% ○ 0208