Chapter 4 Parameter Index
52
Function
code
Parameter LCD display Setting range Factory setting Mod.
MODBUS
address
P1.09
S curve
ascending
segment time
S curve
ascending
segment
10.0-80.0 % (acceleration and
deceleration time)
P1.08+P1.09≤90%
60.0% ○ 0209
P1.10 Stop mode Stop mode
0: Deceleration stop
1: Free stop
2: Deceleration + DC braking
0 × 020A
P1.11
stoppingDC
braking
frequency
Stopping brake
frequency
0.00-MIN(50.00Hz, upper
limit frequency )
2.00Hz ○ 020B
P1.12
stopping
Waiting time of
DC braking at
stop
stopping
Waiting time of
DC braking at
stop
0.00~10.00s 0.00s ○ 020C
P1.13
Set source of
stoppingDC
braking current
at stop
DC
brakingStoppin
g current
source at stop
0: Digital setting
1: Terminal AI1
2: Terminal AI2
3: Terminal AI3 (reserve for
3004GB and below
models)
4: Pulse input
5: Communication setting
Rated current of the motor is
100% current
0 ○ 020D
P1.14
stoppingDC
braking current
at stop
DC
brakingStoppin
g current at
stop
Depend on model
0.0~100.0%
Rated current of the motor is
100% current
0.0% ○ 020E
P1.15
stoppingDC
braking time at
stop
DC braking
Stoppingtime
at stop
0.0~30.0s 0.0s ○ 020F
P1.16
Stop hold
frequency
Stop hold
frequency
0.00-maximum frequency 0.00Hz × 0210
P1.17
Stop Hold
Time
Stop Hold
Time
0.0~3600.0s 0.0s × 0211
P1.18
Braking
selection
Braking
selection
0: Do not use brake
1: Use dynamic braking
2: Use magnetic flux braking
3: Use dynamic and magnetic
flux braking
3 × 0212
P1.19
Dynamic
braking usage
Dynamic
braking usage
30.0%~100.0%
Note: It is active for 3015GB
and below built-in models of
this series; automatically add
dynamic braking in
deceleration
100.0
%
× 0213
P1.20
Instantaneous
stop handling
Instantaneous
stop handling
0: It will be fault Uu1 in case
of instantaneous stop
1: Give an alarm Uu within
instantaneous stop time,
and give fault Uu1
afterwards
2: It will give an alarm Uu in
case of instantaneous stop
0 × 0214
P1.21
Instantaneous
stop time
Instantaneous
stop time
0.5~10.0s
Depend on
model
× 0215