Chapter 4 Parameter Index
87
Function
code
Parameter name
LCD display
Setting range
Setup
Modif
ication
MODBU
S address
1: The control terminal is
closed
2: Output current exceeds
the set point or control
terminal is closed
3: Timing cycle execution
Pd.25
Stall action
toggle level
Stall action
toggle level
100.0~300.0% 200.0% 0E19
Pd.26
Stall action
toggle period
Stall action
toggle period
0.00h~200.0h 0.00h 0E1A
Pd.27
Forward step
frequency
Forward step
frequency
0.00Hz~upper limit
frequency
0.00Hz 0E1B
Pd.28
Forward step
duration
Forward step
duration
0.0s~1000s 0.0s 0E1C
Pd.29
Reverse step
frequency
Reverse step
frequency
0.00Hz~upper limit
frequency
0.00Hz 0E1D
Pd.30
Reverse step
duration
Reverse step
duration
0.0s~1000s 0.0s 0E1E
Pd.31
Forward and
reverse step
interval
Forward and
reverse step
interval
0.0s~1000s 0.0s 0E1F
Pd.32
Number of
repetitions of
step action
Number of
repetitions of
step action
0~100 0 0E20
Pd.33
Software current
limit point
Software current
limit point
0.0%~250.0%
Depend on
models
0E21
Pd.34
Enable hardware
current limit
Enable hardware
current limit
0: Disable; 1: Enable 1 0E22