Chapter 4 Parameter Index
88
PE: Run history record
Function
code
Parameter
name
LCD display
Setting range
Factory
setting
Modif
ication
MODBU
S address
PE.00
Type of
latest fault
Types of
latest faults
0: NULL
1: Uu1 bus undervoltage
2: Uu2 control circuit
undervoltage
3: Uu3 poor charging circuit
4: OC1 acceleration overcurrent
5: OC2 deceleration overcurrent
6: OC3 constant speed
overcurrent
7: Ou1 acceleration overvoltage
8: Ou2 deceleration overvoltage
9: Ou3 constant speed
overvoltage
10: GF Ground
11: OH1 radiator overheat
12: OL1 motor overload
13: OL2 inverter overload
14: SC load short circuit
15: EF0 external fault from an
serial communication
16: EF1 external fault on terminals
17: SP1 input phase loss or
unbalance
18: SPO output phase loss or
unbalance
19: CCF1 control loop fault 1. The
transmission between the
inverter and the keypad still
cannot be established 5s after
powering on
20: CCF2 control loop fault 2.
After connecting the inverter
and the keypad, the
transmission failure last for
more than 2 seconds
21: CCF3 EEPROM failure
22: CCF4 AD translation
exception
23: CCF5 RAM failure
24: CCF6 CPU is disturbed
25: PCE Parameter name
replication error
26: Reserve
27: HE Hall current detection fault
28: De Cut-to-length detection
fault
29: Cue Feed off fault
NULL * 0F00
PE.01
Output
frequency
when the
latest fault
occurs
Output
frequency
when a fault
occurs
0~upper limit frequency 0.00Hz * 0F01