Chapter 4 Parameter Index
89
Function
code
Parameter
name
LCD display
Setting range
Factory
setting
Modif
ication
MODBU
S address
PE.02
Set
frequency
when the
latest fault
occurs
Set
frequency
when a fault
occurs
0~upper limit frequency 0.00Hz * 0F02
PE.03
Output
current
when the
latest fault
occurs
Output
current
when a fault
occurs
0 ~ 2 times of the rated current 0.0A * 0F03
PE.04
DC busbar
voltage
when the
latest fault
occurs
Bus voltage
when a fault
occurs
0~1000V 0V * 0F04
PE.05
Service
condition
when the
latest fault
occurs
Service
condition
when a fault
occurs
0: StP Stop 1: Acc Acceleration 2:
dEc deceleration
3: con Constant speed
StP * 0F05
PE.06
Fault history
(the latest)
Fault
history 1
The same with PE.00 NULL * 0F06
PE.07
Fault history
2
Fault
history 2
The same with PE.00 NULL * 0F07
PE.08
Fault history
3
Fault
history 3
The same with PE.00 NULL * 0F08
PE.09
Accumulate
d running
time
Running
time
0~65530h 0h * 0F09
PE.10
Cumulative
power-on
time
Power-on
time
0~65530h 0h * 0F0A
PE.11
Total
electricity
consumption
(MWh)
Cumulative
electricity
consumptio
n (MWh)
0~9999MWh 0MWh * 0F0B
PE.12
Total
electricity
consumption
(KWh)
Cumulative
electricity
consumptio
n (KWh)
0~999KWh 0KWh * 0F0C