21
C048-740-30 R02, Rev. C (01/2020)
Table 12. Electrical (AM800 Breaker Panel)
Total Load Current 640A Continuous
Load Current Per Pole 100A Continuous
Supported Protection Devices Single-Pole AM Circuit Breaker Up to 125A;
Double-Pole AM Circuit Breaker Up to 200A;
Triple-Pole AM Circuit Breaker Up to 300A;
TPS/TLS Plug-In Fuse Holder
Table 13. Electrical (AM1200 Breaker panel)
Total Load Current 960A Continuous
Load Current Per Pole 100A Continuous
Supported Protection Devices Single-Pole AM Circuit Breaker Up to 125A;
Double-Pole AM Circuit Breaker Up to 200A;
Triple-Pole AM Circuit Breaker Up to 300A;
TPS/TLS Plug-In Fuse Holder
5.3 5.3 GJ Breaker Panel SpecicationsGJ Breaker Panel Specications
Table 14. Mechanical (All Models)
Width 9 in.
Height 20 in.
Depth 11.25 in.
Table 15. Electrical (GJ1200 Breaker Panel)
Total Load Current 960A Continuous
Load Current Per Pole 200A Continuous
Supported Protection Devices Single-Pole GJ Circuit Breaker Up to 250A;
Double-Pole GJ Circuit Breaker Up to 400A;
Triple-Pole GJ Circuit Breaker Up to 700A