Alstom SHPM 101 - 19.19 Checking minimum relay voltage for a fault at the Zone 1 reach point; a) Phase faults

Alstom SHPM 101
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE MANUAL R5888B
QUADRAMHO Chapter 1
Page 24 of 27
Compensation setting = K
N
x Z
Ph
= 0.492 /4.8° x 4.8 /70°
= 2.36
/74.8°
Z
N
= K4 +K5 + K6 /QN°
I
n
Select K4 = 2
K5 = 0.3
K6 = 0.06
θ
N
=75°
Actual Z
N
= 2.36
/75°
Course ground loop impedance = Z
Ph
+ Z
N
= 4.8 /70° + 2.36 /75°
= (1.64 + j4.5) + (0.61 + j2.28)
= (2.25 + j6.78) = 7.14
/71.6°
19.19 Checking minimum relay voltage for a fault at the Zone 1 reach point
a) Phase faults:
Maximum positive sequence impedance behind relay is a maximum JAN source
impedance plus one circuit only of JAN – FEB line.
= 24.9
/88° + 20 x 0.44 /69°
= (0.87 + j24.88) + (3.15 + j8.22)
= (4.02 + J33.1) = 33.3
/83.1°
Impedance to Zone 1 reach point = 8.74
/70° ohms secondary
= 20.96
/70° ohms primary
= (7.17 + j19.7) ohms primary
Total source to Zone reach point impedance
= (4.02 + j33.1) + (7.17 + j19.7)
= (11.19 +j52.8)
= 53.97
/78° ohms primary
For a phase fault voltage seen by relay
= 20.96
/70° x 110
53.97 /78°
Magnitude = 42.7V