EasyManua.ls Logo

Alstom SHPM 101 - 19.19 Checking minimum relay voltage for a fault at the Zone 1 reach point; b) Ground faults

Alstom SHPM 101
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE MANUAL R5888B
QUADRAMHO Chapter 1
Page 25 of 27
b) Ground faults:
Maximum ground loop impedance behind relay is maximum JAN source
ground loop impedance plus ground loop impedance of a JAN – FEB circuit.
Ground loop impedance of JAN source = 24.9
/88° ohms max
Ground loop impedance of JAN – FEB circuit
= 20 x (2 x 0.44
/69° + 1.09 /72°
3
= 20 x (0.32 + j0.82) + (0.33 + j1.04)
3
= (4.33 + j12.4) = 13.13
/70.8° ohms primary
Ground loop impedance behind relay
= 24.9 /88° + 13.13 /70.8°
= 37.6
/82.1°
= (5.17 + j37.2) ohms primary
Ground loop impedance to Zone 1 reach point
= (K11 + K12 + K13) K14 x (Z
Ph
+ Z
N
)
= 1.82 x 7.14
/71.6°
= 13.0
/71.6° ohms secondary
= 31.16
/71.6° ohms primary
= (9.84 + j29.6) ohms primary
Source to Zone 1 reach point ground loop impedance
= (5.17 + j37.2) + (9.84 + j29.6)
= (15.01 + j66.8)
= 68.5
/77.3° ohms
For a ground fault voltage seen by relay
= 31.16 /71.6° x 63.5
68.5 /77.3°
Magnitude = 28.9 volts
For ±5% reach accuracy with the Zone 1 multiplier set to unity, Quadramho
requires at least 2.05V for ground fault measurement, or at least 3.55V for phase
fault measurement. For ±10% accuracy the required voltages are 1.04 and 1.8V
respectively. For Zone 1 multipliers greater than unity, the required relay voltages
for accuracy vary linearly with the multiplier setting.
In this case the Zone 1 multiplier = 1.82. Thus the required voltages for ±5% reach
accuracy are:
1.82 x 2.05 = 3.73 volts for ground faults
1.82 x 3.55 = 6.46 volts for phase faults
Both voltage requirements will be met in this application.

Table of Contents

Related product manuals