AC INPUT CORD
JJJJJJ
The AC input cord is the disconnect device for the electronic load. The plug must be readily identifiable to the
operator. The input cord must be no longer than 3 m (9.84 feet).
The AC input cord we recommend is specified in Table 2.3, “AC Cord Specification”. If you require a special cord, call
our sales representative.
WIRE SIZE TYPE OF CONDUCTOR RATINGS LENGTH (feet)
DIMENSIONS AWG
16/3 SJT 105C 6
18/3 SJT 105C 6
TABLE 2.3 AC CORD SPECIFICATIONS
LOAD WIRING
To select wiring for connecting the load to the electronic load, consider the following factors:
Insulation rating of the wire
Current carrying capacity of the wire
Maximum load wiring length for operation with sense lines
Noise and impedance effects of the load lines
CURRENT CARRYING CAPACITY: As a minimum, load wiring must have a current capacity greater than the output
current rating of the power supply. This ensures that the wiring will not be damaged even if the load is shorted. Table 2.4
shows the maximum current rating, based on 450 A/cm², for various gauges of wire rate for 105C operations. Operate at
the maximum current rating results in an approximately 30C temperature rise for a wire operating in free air. Where
load wiring must operate in areas with elevated ambient temperatures or bundled with other wiring, use larger gauges or
wiring rated for higher temperature.
TABLE 2.4 CURRENT CARRYING CAPACITY FOR LOAD WIRING
WIRE SIZE (AWG) MAXIMUM CURRENT (A)
2/0 303
1/0 247
1 192
2 155
4 97
6 61
8 36
10 21
12 16
14 10