6-60
6
A703: Multipler-A702
This is a multiplier to the math reference input2 selected in A702.
A704: Math Operator
Select the mathematical operation to be carried out between frequency reference selected in A106
and math reference input2 selected in A702 from the following options.
=1: + Add
=2: x Multiply
=3: / Divide
A705: Fix Bias (Hz)
This is fixed bias added into the output after the math operation.
A706: Variable Bias
This parameter can be used to add variable bias into the output after the math operation. Select from
the below options.
=1: Not Used
=2: FSV 0-10V
=3: FSI 4-20mA
=4: VIN 0-10V
=5: IIN 4-20mA
=6: Static Pot
Multiplier
A106: Freq Ref Input
Multiplier
A702: Math Ref Input
A701
A703
Math Operator
A704
+
x/
+
Fix Bias
A705
Variable Bias
A706
Internal Freq
Command