Table-3: 600V Series Axpert-Eazy drive (Terminal and applicable wire for Input and Output)
AMT-XXX-
6
Rated
Current
(A)
Wire
size
Lug size
max
+
Lug
ID
mm
(inch)
Lug
width
mm
(inch)
Terminal
width
mm
(inch)
Hole
diameter
mm
(inch)
Terminal
screw
size
Tightening
torque
N*m
(lb - inch)
mm
2
AWG I/P O/P
011
15 4 12 - - - - - - - 1.92 (17)
015
20 6 10 - - - - - - - 1.92 (17)
018
22 6 10 - - - - - - - 1.92 (17)
022
30 10 8 - - - - - - - 1.92 (17)
030
37 10 8 - - - - - - - 1.92 (17)
037
46 16 6 - - - - - - - 1.92 (17)
045
54 25 4 - - - - - - - 4.3 (38)
055
72 25 4 - - - - - - - 4.3 (38)
075
87 35 2 - - - - - - - 4.3 (38)
090
110 50 1/0 50 x M10
11.0
(0.43)
18.5
(0.73)
19 (0.75) 10.5
(0.41)
M10 22.5 (199)
110
135 70 2/0 70 x M10
11.0
(0.43)
21.4
(0.84)
19 (0.75) 10.5
(0.41)
M10 22.5 (199)
132
150 90 3/0 90 x M10
11.0
(0.43)
25.5
(1.0)
19 (0.75) 10.5
(0.41)
M10 22.5 (199)
160
175 50 x
2p
1/0 x
2p
50 x M10
x 2p
11.0
(0.43)
18.5
(0.73)
30 (1.18) 11.0
(0.43)
M10 22.5 (199)
200
215 70 x
2p
2/0 x
2p
70 x M10
x 2p
11.0
(0.43)
21.4
(0.84)
30 (1.18) 11.0
(0.43)
M10 22.5 (199)
250
290 90 x
2p
3/0 x
2p
90 x M12
x 2p
13.0
(0.51)
25.5
(1.0)
40
(1.58)
38
(1.50)
13.0
(0.51)
M12 31.2 (276)
315
345 150 x
2p
250
kcmil
x 2p
150 x
M12 x 2p
13.0
(0.51)
31.0
(1.22)
40
(1.58)
38
(1.50)
13.0
(0.51)
M12 31.2 (276)
355
387 185 x
2p
300
kcmil
x 2p
185 x
M12 x 2p
13.0
(0.51)
34.2
(1.35)
40
(1.58)
38
(1.50)
13.0
(0.51)
M12 31.2 (276)
+
2p = Two parallel
(Note 3) Breaker for wiring
Install circuit breaker or fuse on the power supply side of the AC DRIVE. Refer to table and select
the Circuit Breaker or Fuses.
(Note 4) Power supply capacity
Make sure that the capacity of the transformer used as the AC DRIVE’s power supply is 10 times
(or less) AC DRIVE capacity (for 4% impedance transformer). If the above value is exceeded,
install an ACL on the AC DRIVE’s input side.
(Note 5) Noise filter
The AC DRIVE will generate high harmonic electromagnetic noise, so using the following noise
measures is recommended.
Insert a noise filter on the input side of the AC DRIVE. Contact Amtech to select the proper noise
filter.
Keep the wiring length between the noise filter and AC DRIVE to 500mm (19.7”) or less.