6-12
6
No.
Parameter
Unit
Def
Min
Max
Res.
Description
WP
B302
Adjustable Over
Current Level
% 300 50 300 1 Set the upper current level as a percentage of
motor rated current. When set to 300%, this
feature is disabled.
B303
Acceleration
Current Limit
% 150 50 200 1 Set the upper current limit as a percentage of
motor rated current for Acceleration.
B304
Under Current
Level
% 0 0 90 1 Set the lower current level as a percentage of
motor rated current for running condition.
B305
Overload Setting % 105 50 105 1 This is reference for timed overload
characteristic. The inverse time characteristics
will change with change in B305.
This overload setting for Heavy Duty.
100 50 100
This overload setting for Normal Duty.
B306
Earth Fault
detection Level
% 50 0 100 1 This parameter sets the earth fault detection
level.
B307
DC Bus Voltage
Control
1 1 3 1 When enabled, it will prevent the overvoltage
during RUN condition.
=1: Disable
=2: Frequency Increase
=3: Stop Deceleration
B308
Reverse Direction
Lock
0 0 1 1 Set this to prevent unintentional reverse
direction operation. When enabled, ensure that
forward direction is selected in A305 (or at
terminal). The AC DRIVE will not start
otherwise.
=0: Disable
=1: Enable
B309
Change Password
0 0 9999 1 User can change the 4-digit user password for
parameter lock.
B310
Parameter Lock 0 0 9999 1 User selectable 4-digit password to prevent
unintentional parameter changes from the digital
operation panel.
B311
Default Value Load
0 0 111 1 The current active parameters will be saved to
non-volatile memory.
222 The saved parameters will be fetched from
memory and now the drive will respond to these
parameters.
333 All default values will be loaded excluding C205
to C218 and B202 to B211 as per 60Hz/460V
(US standard).
444 All default values will be loaded excluding C205
to C218 and B202 to B211 as per 50Hz/415V.
555 When set to 555, the fault history buffer is
cleared. No previous fault codes and related
parameters will be available.
666 All the user parameters will be set to default
including C205 to C218 and B202 to B211 as
per 50Hz/415V.
777 All the PLC parameters will be set to default.
Note:
The value entered in this parameter will not be memorized. It correct value is entered, appropriate action will be taken
and “00” will be displayed. If incorrect value is entered, no action will be taken and “00” will be displayed.
B312
0Hz Overload
Setting
% 105 0 B313 1 For the self-cooling type motor, when operating
at low speed, set these parameters to meet the
motor characteristics.
B313
0.7*BF Overload
Setting
% 105 0 B305 1