CNC Motion Setup/Testing Utility
P/N 70000635C
All rights reserved. Subject to change without notice.
November 2009
32
Save Amp Se
the Signal Gain (F7).”
Saves all modified amplifier parameters to non-volatile memory. This
must be done after performing a signal gain test and/or a balance test.
Balance Test – When Balance test [Balance (F6)] is selected and if the
Communication link between the CNC and ANILAM AC Drive is
enabled/open, the Parameter IAO (Analog 1 Input Offset) will be
displayed and you will be able to modify it by using the up/down arrow
keys. Use right/left arrow to change the increment amount (which is set
on Setup Utility). Save the final value by selecting Save Amp Settings
[MISC (F9)].
Signal Gain Test – When Signal Gain test [SigGain (F7)] is selected and
if the Communication link between the CNC and ANILAM AC Drive is
enabled/open, the Parameter IAS (100% PWM RPM Value) will be
displayed and you will be able to modify it using the up/down arrow keys.
Utility. Save the final value(s) by selecting Save Amp Settings [MISC
(F9)].
These two tests should cover the equivalent of Signal, Balance & Comp
Pots on the analog drives.
Amplifier Test Link
This feature is only for systems equipped with an ANILAM AC Amplifier
(P/N 33001279) and with the Servo Amplifier Communications Cable, P/N
33001389, connected.
This enables/disables the communications monitor. The communications
monitor has two modes of operation: Monitor and Command. Using an
external keyboard, use hot key (
CTRL + F7 t c between the two
mo
Monitor: (Default) During this mode, you can monitor all
communication between the Amplifier and the Control.
Command: During this mode, it not only monitors all communications;
but also, allows you to send direct commands to the
Amplifier.
ttings
This feature is only for systems equipped with an ANILAM AC Amplifier
(P/N 33001279) and with the Servo Amplifier Communications Cable, P/N
33001389, connected. Refer to “Setting the Balance (F6)” and “Setting
Also, the Compensation (equivalent to Comp Pot) parameter GVC
(Velocity Loop Master Gain) will also be displayed; you will be able to
modify it by using right/left arrow keys. Every time you press the arrow
keys, the value will be incremented by the amount entered in the Setup
) o swit h
des.