11.2 Specifications
Specifications are subject to change without notice.
Anker SOLIX X1
System Model X1-P6K-B05-S X1-P6K-B10-S X1-P6K-B15-S X1-P6K-B20-S X1-P6K-B25-S X1-P6K-B30-S
Battery
Battery Type Li-ion (LFP)
Battery Energy Capacity 5 kWh 10 kWh 15 kWh 20 kWh 25 kWh 30 kWh
Number of Battery Modules 1 2 3 4 5 6
AC Output (On-Grid)
Rated Output Power 3 kW 6 kW 6.6 kW
Maximum Output Apparent
Power
3 kVA 6 kVA 6.6 kVA
Rated Output Voltage 220 / 230 / 240 VAC
Rated Frequency 50 / 60 Hz
Power Factor ~1 (+/- 0.8)
THDI (@Rated Power) < 3 %
AC Output (O-Grid)
Rated Output Power 3 kW 6 kW 6.6 kW
1
Peak Output Apparent Power
(Duration)
2
4.5 kVA (10 s) 9 kVA (10 s) 12 kVA (10 s)
Maximum Units in Parallel 6
Rated Output Voltage 220 / 230 / 240 VAC
Frequency Range 50 / 60 Hz
THDU (@Linear Load) < 3 %
Switch Time < 10 ms
Eciency
Round Trip Eciency Up to 90.2 %
3
Connectivity
Internet Connectivity Wi-Fi, Bluetooth, Ethernet, 4G (Option)
Others
Weight 75 kg 126 kg 177 kg 233 kg 284 kg 335 kg
Dimension (W x H x D)
670 × 765 × 150
mm
670 × 1125 × 150
mm
670 × 1485 × 150
mm
670 × 1125 × 150
mm, 670 × 841.5 ×
150 mm
670 × 1485 × 150
mm, 670 × 841.5 ×
150 mm
670 × 1485 × 150
mm, 670 × 1201.5
× 150 mm
Noise
< 35 dB (Ambient Temperature < 40 °C)
< 40 dB (Ambient Temperature > 40 °C)
Mounting Option Ground or Wall
4
Operation Temperature -20 °C to 55 °C
5
Relative Humidity 5 % to 95 % RH
Maximum Operating Altitude Up to 4,000 m, power derating from 2,000 m
6
Assembly Ingress Rating IP65
Warranty 10 Years Limited
7
Grid Connection Certifications Australia: AS/NZS 4777.2