9Tensor
3.4 Performance data
3.4.1 Actuator specications
3.4.2 Specications I-ACT (PMR)
Protection class IP65 (IP 66/IP 67 Option)
Motor • Supply: 85...265 V AC (50/60 Hz) / 24…48 V DC
• Protection: Primary: 2A Tr
• Control: BLDC
• 50/60Hz ±5%, 100% ED
• Isolation class E acc. to DIN EN 60085
Connection 3 cable entries M16x1.5 (customer provided)
Path cutoff Digital via magnet sensor
Ambient temperature -15 °C up to +60 °C (other temperature range optional)
Installation position Arbitrary
Potentiometer (Option) Electronic
Travel 28°…100 revolutions
Function group ash controller, DSP functions
System resolution 12 bit
Set value input Current input max. 0...20 mA, burden 250 W
Voltage input adjustable 0...5 V or 0...10 V
Limited protection against overload and reverse polarity
Actual value transducer Magnetic position sensor on basic board
Actual value output 4...20 mA, 0...20 mA, galvanically isolated
Burden max. 500 Ω, Output stroke max. 10 V
Burden 250 Ω, Output stroke 0...5 V
Operation 3 buttons: Left / MENU / Right
1 switch: AUTO / MANU
Status display via two 7-segment displays