Chapter 3: Configuration and commissioning
42 2X Series Installation Manual
To start night mode at 22:00 and end at midnight, set the night mode start time
for the day to 22:00 and the day mode start time for the following day to 00:00.
Setting the holiday calendar
Select the Holiday calendar option to configure a day or night mode setting for a
range of dates.
To configure day/night mode for dates:
1. Select Panel setup from the Main menu.
2. Select Day/Night mode, and then select Holiday calendar.
3. Select F3 (New) to enter a new holiday period or select an existing holiday
period from the displayed list.
To delete an existing holiday period, press F4 (Delete).
4. Enter the start date and the end date for the holiday sensitivity setting. The
date format is DD/MM (for example, 29/11 for 29 November).
5. Select the sensitivity mode (day or night) for the holiday period. The default
setting is night mode (it is assumed that there are no people on site during the
holiday period).
6. Enter any additional holiday periods as described in steps 3 and 4.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Additional day/night mode settings
Select the Day/Night setup option to configure additional settings such as manual
override of day/night mode schedule and holiday calendar mode changes or
delay behaviour in night mode.
The configuration options available are shown in the table below.
Table 18: Additional day/night mode options
mode
Configures the control panel to process or override sounder, fire routing, and
fire protection delays when the control panel is in night mode.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Day/Night mode, and then select Day/Night setup.