Chapter 3: Configuration and commissioning
62 2X Series Installation Manual
Sounders re-sound
Select the Sounder re-sound option to configure stopped sounder functionality
when new zone alarms are reported. The available configuration options are
shown below. The default setting is YES (sounders re-sound for new zone
alarms).
Note: By default, sounders only re-sound for a new alarm (in the same zone) if a
manual call point alarm is reported following a detector alarm.
Table 26: Sounder re-sound configuration options
YES (default)
A new zone in alarm re-sounds the sounders
NO
A new zone in alarm does not re-sound the sounders
Device
If checked, any new device in alarm in the same zone (including
detectors) re-sounds the sounders.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Sounder re-sound.
3. Select YES or NO.
4. Select and check the Device check box if you want any new device in alarm
in the same zone to re-sound the sounders.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
School bells
Select the School bells option to configure school bell operation and duration (in
seconds). By default school bells are not activated.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select School bells.
3. Select Activate school bells while input is ON, and then select YES or NO.
Select YES for the school bells to sound only while the input is active, or NO if
the bells should continue to sound when the input is off.
4. Select Time, and then enter the duration in seconds (1 to 10).
Enter the school bell duration in seconds if you selected NO in step 3, or
leave the duration blank if you selected YES.
5. Press F4 (Enter), and then press F1 (Back).

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing

Related product manuals