Chapter 3: Configuration and commissioning
2X Series Installation Manual 63
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Self-test
Select the Self-test option to schedule a functional self-test for each loop device
and to generate a daily report in devices that support this feature. By default self-
test is not enabled.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Self-test.
3. Select and check the Enabled check box.
4. Select TestH, and then enter the start time for the self-test (00:00 to 23:59).
5. Select ReportH, and then enter the time for the report to be generated (00:00
to 23:59).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Pulse activation
Select the Pulse activation option to configure the fire routing output activation
pulse time, in milliseconds, for external devices that require pulsed activation. By
default the output activation is continuous.
This option is not available for repeaters or control panels that do not include fire
routing controls.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Pulse Activation.
3. Select and clear the Contin. check box.
4. Select PulseT, and then enter the pulse time value in milliseconds (0 to
10000).
If the PulseT value is 0, the output activation is continuous.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing

Related product manuals