Chapter 3: Configuration and commissioning
88 2X Series Installation Manual
To add a new output group:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Output groups.
A list of the available output groups is displayed.
3. Press F3 (Search), and then enter a number for the new output group that
you want to add.
Press the jog dial to confirm the entry.
4. Select the output group type (PRG, EXTIN, SND, FR, or FP).
5. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
6. Enter a brief text description for the output group.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Output group activation
Output groups can be activated by any of the following:
Zone activation with delays
Output group confirmation for specific outputs (EN 54-2 type C)
Logic rules (configured via the configuration utility PC application)
Manual activation by programmable start/stop buttons (evacuation panels
only)
To avoid unexpected alarm behaviour, consider the activation options when
configuring your fire system. If zone activation is not programmed correctly then
a zone in alarm could override any required confirmation configuration of an
output group.
Delayed output group activation with alarm confirmation
Note: This option is compliant with EN 54 type C alarm confirmation.
Activation of control panel output groups can be delayed based on alarm
confirmation configuration (this may be used, for example, with outputs for
extinguishing devices). The maximum configurable delay is 999 seconds.
The output group alarm confirmation configuration options are shown in the table
below.
Note: Configuration requires that two independent alarm confirmations be
selected from the available options and that a confirmation delay (in seconds) is
entered for the corresponding output group to be activated.

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing

Related product manuals