EasyManua.ls Logo

ASEA AC24 - Automatic Transfer to Generator

ASEA AC24
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC24/30/36 Operations Manual....
41
TRANSFER ON OVERLOAD CONTROL
Feature: Disabled, Select Genset: 1
Enable Disable Forward Back Exit
7.3 LOAD MANAGEMENT OPERATION, cont.
7.3.4 Automatic Transfer to Generator (Converters with Seamless Transfer Option installed)
Upon Shore Alarm, the Automatic Transfer to Generator feature may be used to perform a Seamless
Transfer to a pre-selected generator. This implies connection and setting of the Generator Autostart
Control feature (needed to signal a generator to start and hold the set warm-up time before
transferring). The transfer is not initiated until Voltage Droop has occurred as the load savings
afforded may have taken the converter out of Shore Cord Alarm.
From the front panel, press the SHORE POWER + F2 buttons, and then Transfer (F3) to access the
following screen:
Press the F1 or F2 buttons to adjust the Feature or Select Genset settings; Forward (F3) to advance
the cursor to the Select Genset setting; Back (F4) to return the cursor to the Feature setting, and Exit
(F5) to save the settings and exit the screen. When the cursor is on the Feature setting, the F1/F2
buttons will read Enable/Disable. When the cursor is on the Select Genset setting, the F1/F2 buttons
will read More/Less.
Default Range
Feature DISABLED DISABLED/ENABLED
Genset 1 - 4

Related product manuals