54
Product
presentation
Installation
Settings /
Operation
Servicing and
Warranty
Description of the modes 3.
The product performance is optimized for a continuous power supply operation.
Used to adjust domestic hot water set point temperature to adapt it to
the needs.
Operation at a reduced set point temperature (54° C)
Extended absence : freeze protection of the water heater (15°C)
3.1. Manual mode operation
This operating mode allows the adjustment of the DHW temperature from 50°C to 62°C. This mode will optimize the
production of domestic hot water according to the consumption. To do this, the electric booster pump can be used.
In the case of a Peak hours/Off-peak hours connection, choose a higher set point for more comfort.
Set point temperature: 56°C Minimum set point temperature: 50°C Maximum set point temperature: 62°C
3.2. ECO mode operation
With this mode, the water heater will favor the operation using the heat pump. This mode optimizes the energy
consumption using an ideal set point temperature (54°C) which offers the best efficiency.
This mode is particularly recommended in the case of a continuous power supply.
Depending on the installation conditions (continuous or Peak hours/Off-peak hours) and the room temperature, this
mode may use the electric booster pump.