Element outlet
˚C
‘Shdw’ ‘Max.’ 116
‘Menu**’ 110
F1 F2 F3
The screen indicates that the temperature at the outlet of the compressor element exceeds the
programmed shut-down warning level.
If necessary, stop the compressor by means of stop button (4) and wait until it has stopped.
Switch off the voltage, inspect and remedy.
The warning message will disappear automatically as soon as the warning condition disappears.
A service warning exists
LED (1) is lit. The Main screen will change into a screen similar to the one below:
‘Compr. Outlet’
bar
‘*Serv.Requir.*’
‘Menu**’ ‘**Unld’
F1 F2 F3
The indicators (**) are flashing and the service warning message appears alternately with the
messages indicating whether the compressor runs unloaded or loaded.
Press the key ‘Menu’ (F1) and the tabulator key (2) to select the ‘Status data’ menu: the option
‘Service’ is flashing.
Scroll to this option and select it by pressing the tabulator key (2); following option(s) may flash:
‘Inputs’: if the programmed service level of a component is exceeded (e.g. the maximum
pressure drop over the oil separator element).
‘Plans’: if a service plan interval is exceeded.
Stop the compressor and switch off the voltage.
If the service message was referring to ‘Inputs’ (oil separator): replace the separator element, switch
on the voltage, scroll in the ‘Status data’ menu to ‘Inputs’ and press the ‘Reset’ key to reset the
service message.
If the service message was referring to ‘Plans’: carry out the service actions related to the indicated
plans. Reset the timers of the related plans. Contact your Atlas Copco Customer Centre. See section
Service menu.
A warning message exists
LED (1) is lit and a warning message will appear on the screen.
The indicators (**) are flashing and the warning message appears alternately with the messages
indicating whether the compressor runs unloaded or loaded. This warning indicates that:
On Full-Feature compressors with integrated dryer the dewpoint temperature is too high in
relation to the ambient temperature.
Stop the compressor and switch off the voltage. Inspect the compressor and remedy.
Instruction book
API603130 35