Minimum
setting
Factory
setting
Maximum
setting
Proportional band % 6 10 15
Integration time sec 5 6 10
Parameters
Minimum
setting
Factory
setting
Maximum
setting
Minimum stop time sec 5 5 30
Power recovery time sec 10 10 3600
Restart delay sec 0 0 1200
Communication time-out sec 10 30 60
Fan motor starts per day (air-cooled
compressors)
1 240 240
Protections
Minimum
setting
Factory
setting
Maximum
setting
Compressor element outlet temperature
(shut-down warning level)
˚C 50 110 119
Compressor element outlet temperature
(shut-down warning level)
˚F 122 230 246
Compressor element outlet temperature
(shut-down level)
˚C 111 120 120
Compressor element outlet temperature
(shut-down level)
˚F 232 248 248
Specific protections for Full-Feature compressors:
Minimum
setting
Factory
setting
Maximum
setting
Dewpoint warning temperature ºC 10 25 99
Dewpoint warning temperature ºF 10 77 210
Service plan
The built-in service timers will give a Service warning message after their respective preprogrammed time
interval has elapsed.
For specific data, see section Preventive Maintenance.
Consult Atlas Copco if a timer setting needs to be changed. The intervals must not exceed the nominal
intervals and must coincide logically. See section Modifying general settings.